Type 247D
Interface Connector P6 (Channels 1 to 4)
|
Pin
|
Assignment
|
| 1 |
Signal Ground |
| 2 |
Ch. 1 Transducer Output |
| 3 |
Ch. 1 Scaled Output |
| 4 |
Ch. 1 Set Point Input |
| 5 |
Ch. 2 Set Point Input |
| 6 |
Ch. 3 Set Point Input |
| 7 |
Ch. 4 Set Point Input |
| 8 |
Digital Ground |
| 9 |
Power Ground |
| 10 |
Ch. 2 Flow ON/OFF Input |
| 11 |
Ch. 3 Flow ON/OFF Input |
| 12 |
Ch. 1 Flow ON/OFF Input |
| 13 |
Ch. 4 Flow ON/OFF Input |
| 14 |
Ch. 2 Transducer Output |
| 15 |
Ch. 2 Scaled Output |
| 16 |
Ch. 3 Transducer Output |
| 17 |
CH. 3 Scaled Output |
| 18 |
Ch. 4 Transducer Output |
| 19 |
Ch. 4 Scaled Output |
| 20 |
No Connection |
| 21 |
No Connection |
| 22 |
No Connection |
| 23 |
No Connection |
| 24 |
No Connection |
| 25 |
Chassis Ground |
Interface Connector P5 (Channel 1)
|
Pin
|
Assignment
|
| 1 |
Signal Ground |
| 2 |
Ch. 1 Scaled Output |
| 3 |
Digital Ground |
| 4 |
Power Ground |
| 5 |
No Connection |
| 6 |
Ch. 1 Transducer Output |
| 7 |
External Ratio Set Point Input |
| 8 |
Ratio Output Voltage |
| 9 |
Chassis Ground |
MFC Interface Connectors (J1-J4)
|
Pin
|
Assignment
|
| 1 |
No Connection |
| 2 |
Flow Input Signal |
| 3 |
No Connection |
| 4 |
No Connection |
| 5 |
Power Ground |
| 6 |
-15 Volts |
| 7 |
+15 Volts |
| 8 |
Set Point Output Signal |
| 9 |
No Connection |
| 10 |
Input Stage Output |
| 11 |
No Connection |
| 12 |
Signal Ground |
| 13 |
No Connection |
| 14 |
No Connection |
| 15 |
Chassis Ground |
Download a PDF version of this file.
Note:
This information is subject to change without notice.
Need help?
Contact MKS Instruments by sending an email to MKS or call 800-227-8766 or 978-284-4000 (outside the USA).